50-60HP Cooling Capacity Copper Tube Finned Type Condenser High Efficient Heat Exchanger
Our LG Hot Water Absorption Chiller, Vacuum Pump PVD N360-1, York Centrifugal Chiller occupy a large market space. Our products are based at home and abroad and have been sold in many countries in the world. We actively advocate and strive to practice the spirit of cooperation and win-win situation, which has been widely praised by our global partners and customers. We will continue to uphold our own corporate culture, adhere to our mission and goals, and empower small and medium logistics companies. Since its establishment, our company has grasped the pulse of the market with a steady and pragmatic style, and has won the trust and support of customers with high-quality products and excellent services. We are committed to meeting the needs of our customers. By listening to our customers and understanding their needs, we provide the products, services and solutions that help them succeed.
Follier Cleaner
Flyer's patented product, online filtration, practical and convenient

◇Obtained the utility model patent "self-cleaning refrigerant device" recognized by the State Intellectual Property and Patent Office
◇The lithium bromide special impurity remover is a special equipment matched with the lithium bromide absorption chiller unit
◇This equipment can remove impurities and purify the lithium bromide solution during the operation of the lithium bromide central air-conditioning unit. The purified lithium bromide solution can prolong the service life of the lithium bromide central air conditioning unit, improve the cooling effect, reduce equipment maintenance costs, reduce maintenance time, and save equipment operating costs.
Basic technical parameters

Model FL-3000 FL-6000
Processing capacity 15L/h 3000L/h
Processing accuracy 0.1-0.2um 0.1-0.2um
Filter element model PE30-3 PE30-6
Filter element material Ceramic filter element Ceramic filter element
Number of filter elements 3 roots 6 roots
Packing specification 95*40*40 98*53*42
Product gross weight 50KG 74KG
Material The body of the equipment is made of 316 steel, and the sealing gasket is made of oil-resistant, acid- and alkali-resistant fluorine rubber gasket
Features and Features
●The non-stop filtration design can purify the lithium bromide solution in the machine without affecting the use of the unit.
●The unique design can make the lithium bromide solution be purified in a vacuum environment, effectively preventing the lithium bromide solution from contacting the air.
●Unique filter element structure and blowback design make the filter element have a longer service life and lower operating costs.
●The special filter element specially designed for the impurities generated during the operation of the lithium bromide solution ensures the filtering effect.
●The main material is made of 316 stainless steel, ensuring a longer service life than lithium bromide refrigerators.
●The valve adopts a special valve to ensure air tightness.
●The connection adopts copper tube and high vacuum rubber tube to make the connection more flexible.
●Add auxiliary accessories to purify under shutdown conditions.
special function:
◆This product can be used for new solution filling.
Vacuum cleaner
a. Make sure to close the unit's dilute solution valve, unit's concentrated solution valve, open the liquid inlet valve and the liquid return valve on the decontamination device, close the drain valve, and connect the exhaust valve to the unit's vacuum device;
b. Start the vacuum pump and slowly open the exhaust valve for pumping. When the pressure vacuum gauge shows the value or close to -0.1MPa, close the exhaust valve, and then maintain the pressure for one hour, and the vacuum without rebound is regarded as qualified;
c. If there is a vacuum rebound, check whether there is any leakage at the flange of the piping and the cleaner body. After the treatment, follow the above steps until the vacuum is qualified.
Filter operation of the dust remover
a. First/close all valves, then open the unit's dilute solution valve, unit's concentrated solution valve and return valve;
b. Slowly open the inlet valve, and the degree of opening shall be subject to no obvious influence on the normal circulation of the unit;
c. Record the date of use after the operation is stable to determine the backwash and blowdown.
Backwash blowdown operation
a. After operating for 7 days, close the inlet valve and outlet valve;
b. Open the drain valve;
c. Connect nitrogen to the recoil valve and slowly open the recoil valve for backwashing;
d. When the erosion degree of the solution at the outlet of the blowdown valve becomes smaller, close the recoil valve and the blowdown valve at the same time;
We focus on product development and technological innovation, and design and produce our 50-60HP Cooling Capacity Copper Tube Finned Type Condenser High Efficient Heat Exchanger with scientific and stable concepts. Our company has won the trust and praise of users with excellent product quality, enthusiastic after-sales service and reasonable sales price. Our industrial layout is gradually optimized, our market advantage position is constantly consolidated, our influence is continuously enhanced, and our profit prospects are promising.