Heat Exchanger Explosion-Proof Cold Water Cooling Chiller
We guarantee that our Centrifugal Chiller, Hot Water Absorption Chiller, Shell And Tube For Shuangliang Chiller is reliable and that its performance and functionality meet the requirements of our customers within the permitted range. The success of our enterprise depends on many factors of the enterprise, but the talent strategy is one of the core of the whole enterprise development strategy. With the increasing demand for domestic and international markets, we will improve quality, increase product variety, under the premise of further expansion. We'll try our best to serve you the highest quality products with most competitive price.
Follier Cleaner
Flyer's patented product, online filtration, practical and convenient

◇Obtained the utility model patent "self-cleaning refrigerant device" recognized by the State Intellectual Property and Patent Office
◇The lithium bromide special impurity remover is a special equipment matched with the lithium bromide absorption chiller unit
◇This equipment can remove impurities and purify the lithium bromide solution during the operation of the lithium bromide central air-conditioning unit. The purified lithium bromide solution can prolong the service life of the lithium bromide central air conditioning unit, improve the cooling effect, reduce equipment maintenance costs, reduce maintenance time, and save equipment operating costs.
Basic technical parameters

Model FL-3000 FL-6000
Processing capacity 15L/h 3000L/h
Processing accuracy 0.1-0.2um 0.1-0.2um
Filter element model PE30-3 PE30-6
Filter element material Ceramic filter element Ceramic filter element
Number of filter elements 3 roots 6 roots
Packing specification 95*40*40 98*53*42
Product gross weight 50KG 74KG
Material The body of the equipment is made of 316 steel, and the sealing gasket is made of oil-resistant, acid- and alkali-resistant fluorine rubber gasket
Features and Features
●The non-stop filtration design can purify the lithium bromide solution in the machine without affecting the use of the unit.
●The unique design can make the lithium bromide solution be purified in a vacuum environment, effectively preventing the lithium bromide solution from contacting the air.
●Unique filter element structure and blowback design make the filter element have a longer service life and lower operating costs.
●The special filter element specially designed for the impurities generated during the operation of the lithium bromide solution ensures the filtering effect.
●The main material is made of 316 stainless steel, ensuring a longer service life than lithium bromide refrigerators.
●The valve adopts a special valve to ensure air tightness.
●The connection adopts copper tube and high vacuum rubber tube to make the connection more flexible.
●Add auxiliary accessories to purify under shutdown conditions.
special function:
◆This product can be used for new solution filling.
Vacuum cleaner
a. Make sure to close the unit's dilute solution valve, unit's concentrated solution valve, open the liquid inlet valve and the liquid return valve on the decontamination device, close the drain valve, and connect the exhaust valve to the unit's vacuum device;
b. Start the vacuum pump and slowly open the exhaust valve for pumping. When the pressure vacuum gauge shows the value or close to -0.1MPa, close the exhaust valve, and then maintain the pressure for one hour, and the vacuum without rebound is regarded as qualified;
c. If there is a vacuum rebound, check whether there is any leakage at the flange of the piping and the cleaner body. After the treatment, follow the above steps until the vacuum is qualified.
Filter operation of the dust remover
a. First/close all valves, then open the unit's dilute solution valve, unit's concentrated solution valve and return valve;
b. Slowly open the inlet valve, and the degree of opening shall be subject to no obvious influence on the normal circulation of the unit;
c. Record the date of use after the operation is stable to determine the backwash and blowdown.
Backwash blowdown operation
a. After operating for 7 days, close the inlet valve and outlet valve;
b. Open the drain valve;
c. Connect nitrogen to the recoil valve and slowly open the recoil valve for backwashing;
d. When the erosion degree of the solution at the outlet of the blowdown valve becomes smaller, close the recoil valve and the blowdown valve at the same time;
We strive to promote the rapid development of the company in a new starting point to achieve new breakthroughs, and lay a good foundation for the company to become an excellent manufacturer of providing Heat Exchanger Explosion-Proof Cold Water Cooling Chiller with characteristics. We persistently strive for progress through wind and rain, and hope to realize our pursuit and dream with the enterprise spirit of not forgetting the beginning. We tirelessly pursue strict product quality standards, and provide all-round and integrated services to meet customer consultation, design, customization, installation and after-sales needs.
You Might Also Like