Causes of condensation during fan coil air conditioning operation
When the fan coil unit air conditioner operates in summer, sometimes there is fog when supplying cold air to the room, and sometimes there is condensate at the air supply outlet. The main reasons are as follows:
1) When the unit starts to operate, due to the high humidity in the air-conditioned room, its dew point temperature is high and far higher than the air supply temperature. When the air from the fan coil unit mixes with the air around the air outlet, the air reaches the supersaturated state, so a large amount of fog is generated. At the same time, at the air supply outlet, when the temperature of the air outlet components is lower than the air dew point temperature, there will also be condensate precipitation. In this regard, if the fan coil has a water volume regulating switch, the water volume can be reduced, the water temperature can be increased, and the fog phenomenon can be improved. After the unit has operated for a period of time, the dew point temperature of the air will also decrease correspondingly due to the reduction of the indoor temperature, and then the fog phenomenon will gradually disappear.
2) In the process of processing the coil and sleeve of some fan coils, the sleeve processing is not good, the coil is not closely contacted with the sleeve, and the surface temperature of the coil is too low, which will cause condensation on the surface of the coil. A large amount of condensate will stay on the surface of the coil and cannot flow into the drip pan in time. When the fan is supplying air, some condensate will often be blown out with the wind.
For tall buildings, when the height of the single floor space of the building is more than 10 m. The volume of the space is more than 10000 m3, and the ratio of the height of the area requiring air conditioning to the space height of the building on this floor is less than 1/2, layered air conditioning can be considered.

Layered air conditioning is an air conditioning mode that air conditioning is applied to the lower area of the space, that is, the part required by the human body and the process, while air conditioning is not applied to the upper area. Compared with full room air conditioning, layered air conditioning can save energy by 20%~30% in summer, and reduce initial investment and energy consumption. However, in winter, the hot air does not save energy due to its upward action.
In case of layered air conditioning, the air supply outlet center is taken as the layered surface, and the entire tall building space is vertically divided into two areas. The space below is an air-conditioned area, and the space above is a non air-conditioned area. Air conditioning shall be carried out in the air conditioning area according to the temperature and humidity parameters that must be guaranteed according to the requirements of human comfort or production process. The height of general comfort air conditioner can be 2m, and the technological air conditioner must be determined according to the height of the equipment.

Production Application
The company’s main business scope includes: central air-conditioning maintenance, cleaning and technical services; cooling tower and fan coil cleaning and maintenance services; custom processing of lithium bromide solution; sales of lithium bromide solution special impurity separators; central air-conditioning host and various zero Sales of accessories; installation and sales of central air conditioning systems, etc.
Widely used in major air-conditioning systems and process refrigeration cold and heat sources; in steel, textile, chemical, electronics, pharmaceutical, food and other industrial and mining enterprises, as well as hotels, theaters, hospitals, and large commercial buildings , Central heating stations and other occasions are widely used.
Contact Us
Ms. Guo- Sales Support & Operations Manager.
Email: mdguolijuan@zjflier.com
Mob: +8615358588768
WeChat: + 86 15358588768
WhatsApp: +86 15358588768