How to shut down and maintain lithium bromide chillers in winter

How to shut down and maintain lithium bromide chillers in winter

 

What is the method of shutdown and maintenance of lithium bromide units in winter?

1. Vacuum:

For lithium bromide units that are not filled with nitrogen for maintenance, record the vacuum indication on the generator of the unit. Once any changes are found, immediately vacuumize and consult the refrigerator manufacturer for the next step. It is recommended that the user fill the unit with nitrogen for protection, which saves worry and effort.

2. Draining water:

This includes draining cold water, cooling water, hot water (if it is a steam-type unit, it is steam condensate), and all water that communicates with the unit. Note that it is necessary to ensure that no water leaks after the relevant valve is closed, otherwise it is necessary to set a water drain valve at the lowest part of the pipeline and always open so that the leaked water can flow out without entering the lithium bromide unit.

3. Electrical:

Including damage to electronic components such as sensors, and motor insulation of pumps.

4. Oil change:

This is often overlooked by most users of lithium bromide units. Because the old oil contains water, it will corrode the vacuum pump body if it is shut down for a long time.

5. Solution:

Part of the solution is pumped into the evaporator. This process is cumbersome to operate, and different manufacturers have different machine processing methods, so it is best to be handled by professional and technical personnel. The general method is: in the summer when the refrigerator is running at full load, a part of the solution is drawn from the outlet of the solution pump of the refrigerator and stored in advance, and then filled into the evaporator when it is shut down in winter.

I hope everyone can understand the above methods of shutdown and maintenance of lithium bromide units in winter.