The importance of understanding the high temperature of chillers
The temperature of the high-voltage generator (hereinafter referred to as the high generator) is a very important parameter in the lithium bromide unit, which directly affects the refrigeration output of the unit.
"High voltage generator"
The main function of Gaofa is to heat the lithium bromide solution, separate the water inside the solution, and generate refrigerant vapor. The separation of refrigerant vapor also leads to an increase in the concentration of the solution at the outlet of the generator.
Under other unchanged conditions, the higher the temperature of the high engine, the higher the refrigerant vapor pressure and spray concentration - that is, the higher the high engine temperature, the higher the refrigeration output of the unit.
influence
The lithium bromide absorption chiller can achieve stepless regulation of cooling capacity from 20% to 100% during use, and its main regulation method is to control the high temperature of the generator. By controlling the flow rate or consumption of the heat source supply, the high temperature can be intuitively changed.
Based on practical experience, we suggest adjusting the long-term load of the unit between 40% and 80%, which is beneficial for extending the service life of the unit and also takes into account the economy of daily use. Corresponding to the load, it is recommended to control the high engine temperature between 100 ℃ and 152 ℃ for smooth operation.
Although the high engine temperature is directly proportional to the refrigeration output of the unit, we do not recommend raising the high engine temperature above 160 ℃ during daily operation. Due to the high incidence of high temperature and high pressure, it may cause the following impacts:
1. Increase the risk of solution crystallization
One of the methods to increase the refrigeration capacity of a unit is to increase the supply of heat sources and increase the high temperature of the generator. But as the heating steam pressure increases, the mass fraction of the concentrated solution increases, and the unit operates under high load conditions, which is more likely to cause crystallization;
2. Damaged equipment
There is a risk of corrosion inhibitor decomposition in lithium bromide solution at high temperatures. After the corrosion inhibitor decomposes, the protective film inside the unit cavity will be damaged, leading to serious corrosion. In addition, the decomposition products of the corrosion inhibitor may block the exchanger. The above potential risks will significantly shorten the service life of the unit;
3. Increase energy consumption.
A higher heating temperature means that more heat is needed for heating, which will increase the energy consumption of the unit;
4. Fault shutdown
When the high temperature is too high, the pressure and solution concentration increase accordingly, which can easily generate high pressure alarm and high solution concentration alarm. Both of these alarm phenomena can cause the unit to immediately trip and seriously affect operation;
5. Refrigerant water pollution
The higher the temperature, the more intense the boiling of the solution inside the unit. When the boiling is too intense, the generator solution will be entrained into the condenser, causing refrigerant water pollution, resulting in a decrease in refrigeration capacity and an increase in crystallization risk;
Secondly, we must ensure that the trend of high temperature changes is stable. Both the heating and cooling processes should continue for a period of time to allow the high temperature to gradually change; When the unit meets the stable operating conditions of load formation, the high temperature should be maintained within 5 ℃ above and below. If the high temperature fluctuates violently, even if the refrigeration output is normal, the operation of the unit is still abnormal at this time.
summary
In summary, in order to ensure the refrigeration capacity and stable operation of lithium bromide units, it is necessary to accurately monitor the heat source consumption (flow rate) and high generation temperature, ultimately achieving a working condition where the refrigeration capacity matches the usage load and the high generation temperature matches the refrigeration capacity.
Lithium bromide solution manufacturer
About us
Flier Refrigeration Engineering Technology Co., Ltd is a professional technical service enterprise integrating central air-conditioning host sales, spare parts sales, unit repair and maintenance.

Factory located in Zhenjiang, Jiangsu, covering an area of 25,000 square meters ,and has been built with 1 R&D center, 1 pilot plant, 3 An innovative production, learning, and research base composed of a professional production workshop and its corresponding infrastructure. At present, the company has become a well-known technical service provider in the field of central air conditioning in China.
The company's main business scope includes: central air-conditioning maintenance, cleaning and technical services; cooling tower and fan coil cleaning and maintenance services; custom processing of lithium bromide solution; sales of lithium bromide solution special impurity separators; central air-conditioning host and various zero Sales of accessories; installation and sales of central air conditioning systems, etc.
Contact us
Ms. Lillian GUO
Zhenjiang FLIER Refrigeration Engineering Technology Co., Ltd
Jiangsu, China
Tel: + 86 15358588768(Whatsapp)
Wechat:15358588768
E-mail: mdguolijuan@zjflier.com