Coping With Crystallization Of Lithium Bromide Solution During Shutdown

1. Crystallization during shutdown is caused by insufficient dilution of the solution during shutdown or too low ambient temperature. Once the crystallization solution pump cannot operate. Steam can be used to heat the shell and inlet until the pump is operational. Heating is to pay attention to do not let steam and condensate into the motor and control equipment, do not directly heat the motor.


2. Check the vacuum pressure gauge at the outlet of the solution pump. If the pressure indicator of the vacuum gauge is 1 atmosphere (i.e., the pressure gauge indicates 0), the crystallization in the pump and at the outlet is not treated; If the pressure gauge indicates a high vacuum, it indicates that the pump is not running and some crystallization occurs in the machine, so steam heating should be continued. When the pump is running, if the indicated pressure on the vacuum pressure gauge is higher than atmospheric pressure, it indicates that the crystallization has dissolved. Sometimes, the sampler can be used to sample, observe the spray of the absorber, and check whether the absorber has liquid level, but also listen to the pump outlet in the sound of the flow of the solution to determine whether it has been dissolved.