Lithium bromide absorption refrigerating machine because the vertical height of the generator steam space is too small, cooling steam flow rate is too high or liquid baffle plate structure is bad, or due to the sudden rise of heating steam pressure, dilute solution concentration is low, the pH of the solution is too large, the reason such as the cooling water temperature is too low and cause solution strongly boiling in the generator, the generator of the lithium bromide beads was cooling steam into the condenser; Absorber lithium bromide droplets may also splash into the evaporator, causing water pollution of refrigerant.
The color of refrigerant water can be observed from the evaporator liquid capsule lens, and it is found that the refrigerant water is yellow, which is suspected of pollution. At this time, the refrigerant water sampling valve can be used to sample and determine the density of the refrigerant water. If the measured density is not greater than 1.04kg/ L, it is generally not treated. When greater than 1.04kg/ L, the coolant water can be regenerated through the coolant water bypass valve, until the density of the coolant water reaches the standard.