Operation Specification For Starting And Stopping Of Lithium Bromide Refrigeration Unit

First, the guidance process

1. Open the refrigerant water and cooling water valve of the system, start the refrigerant water and cooling water pump, and check whether the flow of the refrigerant water and cooling water meets the operation requirements of the equipment.

2. Start generator, absorption pump, and adjust high and low ignition level.

3. Open the condensate bypass valve of the trap, and slowly add steam to gradually heat up the equipment, and pay attention to the high level of the liquid.

4. After the evaporator coolant level rises, start the evaporator pump and close the trap bypass valve.


Two, shutdown procedures

1. Turn off steam.

2. After the equipment continues to run for 20 minutes, close the solution pump (make the dilute solution fully mixed to prevent crystallization of the equipment).

3. Stop the cooling water and refrigerant water pump.


Three, emergency stop

During the operation of lithium bromide refrigerator, if any of the following situations occur, it should immediately close the steam valve, bypass the cooling water to the absorber, open the condensate bend bypass valve, and then try to stop normally.

1. Cooling water, cut off refrigerant water.

2. Generator, evaporator, any one of the absorber pump are not working properly.

3. The electricity.